Home | INDUSTRIAL PURE WATER APPLICATION | Highly Purified Water (HPW) for pharmaceutical use
INDUSTRIAL PURE WATER APPLICATION
Highly Purified Water (HPW) for pharmaceutical use
Ultra pure water reverse osmosis water purification system with EDI for WFI 15m3/h
1. Specifications
Model | Chem500 | Chem1000 | Chem2000 | Chem3000 | |
Process flow | Booster pump+sand/softener/activated carbon+precision filter+RO+EDI | ||||
OperationParameter | |||||
Raw water | municipal water: TDS<300ppm, 5-35℃, 2.0-4.0 Kgf/cm2 | ||||
Feed flow | L/h | 1000 | 1500 | 3000 | 4500 |
Permeate water capacity | L/h | 500 | 1000 | 2000 | 3000 |
Recovery rate | % | 62.5 | 66.7 | 66.7 | 66.7 |
Resisvity | MΩ | >5 | |||
Power | KW | 2 | 3 | 4 | 6.5 |
Pretreatment filteration system | |||||
Head Pressure | m | 40 | |||
Multi-media filter size | mm | 300x1500 | 450x1500 | 500x1500 | 600x1500 |
Automatic control valve | |||||
Activated carbon filter | mm | 300x1500 | 450x1500 | 500x1500 | 600x1500 |
Automatic control valve | |||||
Water softener | mm | 300x1500 | 450x1500 | 500x1500 | 600x1500 |
twin-softener, uninterrupted service flow, automatic control valve regeneration | |||||
Valves and piping | SS304/UPVC depend on application purpose | ||||
RO main water treatment system | |||||
High pressure pump flow | m3/h | 1 | 1.6 | 3.2 | 5 |
Head pressure | m | 180 (inverter control) | |||
Power | kw | 1.5 | 2.2 | 3 | 4 |
RO membrane element | 4040x3 | 4040x6 | 4040x10 | 4040x15 | |
Instrument | Flow transmitter, pressure gauge, conductivity meter, resistivity meter | ||||
Electric control system | Siemens PLC & touchscreen, Schneider | ||||
Documents |
DQ/IQ/OQ, and assist clients to fulfill PQ, FAT/SAT report |
2. Description:
3. Applications:
Potable water |
Ice manufacturing |
Cooling tower |
Plating operations |
Rinse water |
Power plants |
Electronics |
Beverage production |
Metal finishing |
Mining industry |
Bottled water |
Safe drinking water |
WFI ( water for injection) | Pharmacy / Pharmaceutical | Dialysis |
4. Competitive Advantage: